1910.253(a)
General requirements. -
1910.253(a)(1)
Flammable mixture. Mixtures of fuel gases and air or oxygen may be explosive and shall be guarded
against. No device or attachment facilitating or permitting mixtures of air or oxygen with flammable gases prior to consumption, except at the burner
or in a standard torch, shall be allowed unless approved for the purpose.
1910.253(a)(2)
Maximum pressure. Under no condition shall acetylene be generated, piped (except in approved
cylinder manifolds) or utilized at a pressure in excess of 15 psig (103 kPa gauge pressure) or 30 psia (206 kPa absolute). (The 30 psia (206 kPa
absolute) limit is intended to prevent unsafe use of acetylene in pressurized chambers such as caissons, underground excavations or tunnel
construction.) This requirement is not intended to apply to storage of acetylene dissolved in a suitable solvent in cylinders manufactured and
maintained according to U.S. Department of Transportation requirements, or to acetylene for chemical use. The use of liquid acetylene shall be
prohibited.
..1910.253(a)(3)
1910.253(a)(3)
Apparatus. Only approved apparatus such as torches, regulators or pressure-reducing valves,
acetylene generators, and manifolds shall be used.
1910.253(a)(4)
Personnel. Workmen in charge of the oxygen or fuel-gas supply equipment, including generators, and
oxygen or fuel-gas distribution piping systems shall be instructed and judged competent by their employers for this important work before being left
in charge. Rules and instructions covering the operation and maintenance of oxygen or fuel-gas supply equipment including generators, and oxygen or
fuel-gas distribution piping systems shall be readily available.
1910.253(b)
Cylinders and containers -
1910.253(b)(1)
Approval and marking.
1910.253(b)(1)(i)
All portable cylinders used for the storage and shipment of compressed gases shall be constructed
and maintained in accordance with the regulations of the U.S. Department of Transportation, 49 CFR Parts 171-179.
..1910.253(b)(1)(ii)
1910.253(b)(1)(ii)
Compressed gas cylinders shall be legibly marked, for the purpose of identifying the gas
content, with either the chemical or the trade name of the gas. Such marking shall be by means of stenciling, stamping, or labeling, and shall not be
readily removable. Whenever practical, the marking shall be located on the shoulder of the cylinder. This method conforms to the American National
Standard Method for Marking Portable Compressed Gas Containers to Identify the Material Contained, ANSI Z48.1-1954, which is incorporated by reference
as specified in Sec. 1910.6.
1910.253(b)(1)(iii)
Compressed gas cylinders shall be equipped with connections complying with the American
National Standard Compressed Gas Cylinder Valve Outlet and Inlet Connections, ANSI B57.1-1965, which is incorporated by reference as specified in Sec.
1910.6.
1910.253(b)(1)(iv)
All cylinders with a water weight capacity of over 30 pounds (13.6 kg) shall be equipped with
means of connecting a valve protection cap or with a collar or recess to protect the valve.
1910.253(b)(2)
Storage of cylinders-general.
1910.253(b)(2)(i)
Cylinders shall be kept away from radiators and other sources of heat.
1910.253(b)(2)(ii)
Inside of buildings, cylinders shall be stored in a well-protected, well-ventilated, dry
location, at least 20 (6.1 m) feet from highly combustible materials such as oil or excelsior. Cylinders should be stored in definitely assigned
places away from elevators, stairs, or gangways. Assigned storage spaces shall be located where cylinders will not be knocked over or damaged by
passing or falling objects, or subject to tampering by unauthorized persons. Cylinders shall not be kept in unventilated enclosures such as lockers
and cupboards.
..1910.253(b)(2)(iii)
1910.253(b)(2)(iii)
Empty cylinders shall have their valves closed.
1910.253(b)(2)(iv)
Valve protection caps, where cylinder is designed to accept a cap, shall always be in place,
hand-tight, except when cylinders are in use or connected for use.
1910.253(b)(3)
Fuel-gas cylinder storage. Inside a building, cylinders, except those in actual use or attached
ready for use, shall be limited to a total gas capacity of 2,000 cubic feet (56 m(3)) or 300 pounds (135.9 kg) of liquefied petroleum gas.
1910.253(b)(3)(i)
For storage in excess of 2,000 cubic feet (56 m(3)) total gas capacity of cylinders or 300 pounds
(135.9 kg) of liquefied petroleum gas, a separate room or compartment conforming to the requirements specified in paragraphs (f)(6)(i)(H) and
(f)(6)(i)(I) of this section shall be provided, or cylinders shall be kept outside or in a special building. Special buildings, rooms or compartments
shall have no open flame for heating or lighting and shall be well ventilated. They may also be used for storage of calcium carbide in quantities not
to exceed 600 (271.8 kg) pounds, when contained in metal containers complying with paragraphs (g)(1)(i) and (g)(1)(ii) of this section.
1910.253(b)(3)(ii)
Acetylene cylinders shall be stored valve end up.
..1910.253(b)(4)
1910.253(b)(4)
Oxygen storage.
1910.253(b)(4)(i)
Oxygen cylinders shall not be stored near highly combustible material, especially oil and grease;
or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near any other substance likely to cause or accelerate fire; or in an
acetylene generator compartment.
1910.253(b)(4)(ii)
Oxygen cylinders stored in outside generator houses shall be separated from the generator or
carbide storage rooms by a noncombustible partition having a fire-resistance rating of at least 1 hour. This partition shall be without openings and
shall be gastight.
1910.253(b)(4)(iii)
Oxygen cylinders in storage shall be separated from fuel-gas cylinders or combustible materials
(especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance
rating of at least one-half hour.
1910.253(b)(4)(iv)
Where a liquid oxygen system is to be used to supply gaseous oxygen for welding or cutting and
the system has a storage capacity of more than 13,000 cubic feet (364 m(3)) of oxygen (measured at 14.7 psia (101 kPa) and 70 deg. F (21.1 deg. C)),
connected in service or ready for service, or more than 25,000 cubic feet (700 m(3)) of oxygen (measured at 14.7 psia (101 kPa) and 70 deg. F (21.1
deg. C)), including unconnected reserves on hand at the site, it shall comply with the provisions of the Standard for Bulk Oxygen Systems at Consumer
Sites, NFPA No. 566-1965, which is incorporated by reference as specified in Sec. 1910.6.
..1910.253(b)(5)
1910.253(b)(5)
Operating procedures.
1910.253(b)(5)(i)
Cylinders, cylinder valves, couplings, regulators, hose, and apparatus shall be kept free from
oily or greasy substances. Oxygen cylinders or apparatus shall not be handled with oily hands or gloves. A jet of oxygen must never be permitted to
strike an oily surface, greasy clothes, or enter a fuel oil or other storage tank.
1910.253(b)(5)(ii)
1910.253(b)(5)(ii)(A)
When transporting cylinders by a crane or derrick, a cradle, boat, or suitable platform shall
be used. Slings or electric magnets shall not be used for this purpose. Valve-protection caps, where cylinder is designed to accept a cap, shall
always be in place.
1910.253(b)(5)(ii)(B)
Cylinders shall not be dropped or struck or permitted to strike each other
violently.
1910.253(b)(5)(ii)(C)
Valve-protection caps shall not be used for lifting cylinders from one vertical position to
another. Bars shall not be used under valves or valve-protection caps to pry cylinders loose when frozen to the ground or otherwise fixed; the use of
warm (not boiling) water is recommended. Valve-protection caps are designed to protect cylinder valves from damage.
1910.253(b)(5)(ii)(D)
Unless cylinders are secured on a special truck, regulators shall be removed and
valve-protection caps, when provided for, shall be put in place before cylinders are moved.
1910.253(b)(5)(ii)(E)
Cylinders not having fixed hand wheels shall have keys, handles, or nonadjustable wrenches on
valve stems while these cylinders are in service. In multiple cylinder installations only one key or handle is required for each manifold.
..1910.253(b)(5)(ii)(F)
1910.253(b)(5)(ii)(F)
Cylinder valves shall be closed before moving cylinders.
1910.253(b)(5)(ii)(G)
Cylinder valves shall be closed when work is finished.
1910.253(b)(5)(ii)(H)
Valves of empty cylinders shall be closed.
1910.253(b)(5)(ii)(I)
Cylinders shall be kept far enough away from the actual welding or cutting operation so that
sparks, hot slag, or flame will not reach them, or fire-resistant shields shall be provided.
1910.253(b)(5)(ii)(J)
Cylinders shall not be placed where they might become part of an electric circuit. Contacts
with third rails, trolley wires, etc., shall be avoided. Cylinders shall be kept away from radiators, piping systems, layout tables, etc., that may be
used for grounding electric circuits such as for arc welding machines. Any practice such as the tapping of an electrode against a cylinder to strike
an arc shall be prohibited.
1910.253(b)(5)(ii)(K)
Cylinders shall never be used as rollers or supports, whether full or empty.
1910.253(b)(5)(ii)(L)
The numbers and markings stamped into cylinders shall not be tampered with.
..1910.253(b)(5)(ii)(M)
1910.253(b)(5)(ii)(M)
No person, other than the gas supplier, shall attempt to mix gases in a cylinder. No one,
except the owner of the cylinder or person authorized by him, shall refill a cylinder.
1910.253(b)(5)(ii)(N)
No one shall tamper with safety devices in cylinders or valves.
1910.253(b)(5)(ii)(O)
Cylinders shall not be dropped or otherwise roughly handled.
1910.253(b)(5)(ii)(P)
Unless connected to a manifold, oxygen from a cylinder shall not be used without first
attaching an oxygen regulator to the cylinder valve. Before connecting the regulator to the cylinder valve, the valve shall be opened slightly for an
instant and then closed. Always stand to one side of the outlet when opening the cylinder valve.
1910.253(b)(5)(ii)(Q)
A hammer or wrench shall not be used to open cylinder valves. If valves cannot be opened by
hand, the supplier shall be notified.
1910.253(b)(5)(ii)(R)
-
1910.253(b)(5)(ii)(R)(1)
Cylinder valves shall not be tampered with nor should any attempt be made to repair them.
If trouble is experienced, the supplier should be sent a report promptly indicating the character of the trouble and the cylinder's serial number.
Supplier's instructions as to its disposition shall be followed.
1910.253(b)(5)(ii)(R)(2)
Complete removal of the stem from a diaphragm-type cylinder valve shall be
avoided.
..1910.253(b)(5)(iii)
1910.253(b)(5)(iii)
-
1910.253(b)(5)(iii)(A)
Fuel-gas cylinders shall be placed with valve end up whenever they are in use. Liquefied
gases shall be stored and shipped with the valve end up.
1910.253(b)(5)(iii)(B)
Cylinders shall be handled carefully. Rough handling, knocks, or falls are liable to damage
the cylinder, valve or safety devices and cause leakage.
1910.253(b)(5)(iii)(C)
Before connecting a regulator to a cylinder valve, the valve shall be opened slightly and
closed immediately. The valve shall be opened while standing to one side of the outlet; never in front of it. Never crack a fuel-gas cylinder valve
near other welding work or near sparks, flame, or other possible sources of ignition.
1910.253(b)(5)(iii)(D)
Before a regulator is removed from a cylinder valve, the cylinder valve shall be closed and
the gas released from the regulator.
1910.253(b)(5)(iii)(E)
Nothing shall be placed on top of an acetylene cylinder when in use which may damage the
safety device or interfere with the quick closing of the valve.
1910.253(b)(5)(iii)(F)
If cylinders are found to have leaky valves or fittings which cannot be stopped by closing
of the valve, the cylinders shall be taken outdoors away from sources of ignition and slowly emptied.
..1910.253(b)(5)(iii)(G)
1910.253(b)(5)(iii)(G)
A warning should be placed near cylinders having leaking fuse plugs or other leaking safety
devices not to approach them with a lighted cigarette or other source of ignition. Such cylinders should be plainly tagged; the supplier should be
promptly notified and his instructions followed as to their return.
1910.253(b)(5)(iii)(H)
Safety devices shall not be tampered with.
1910.253(b)(5)(iii)(I)
Fuel-gas shall never be used from cylinders through torches or other devices equipped with
shutoff valves without reducing the pressure through a suitable regulator attached to the cylinder valve or manifold.
1910.253(b)(5)(iii)(J)
The cylinder valve shall always be opened slowly.
1910.253(b)(5)(iii)(K)
An acetylene cylinder valve shall not be opened more than one and one-half turns of the
spindle, and preferably no more than three-fourths of a turn.
1910.253(b)(5)(iii)(L)
Where a special wrench is required it shall be left in position on the stem of the valve
while the cylinder is in use so that the fuel-gas flow can be quickly turned off in case of emergency. In the case of manifolded or coupled cylinders
at least one such wrench shall always be available for immediate use.
..1910.253(c)
1910.253(c)
Manifolding of cylinders -
1910.253(c)(1)
Fuel-gas manifolds.
1910.253(c)(1)(i)
Manifolds shall be approved either separately for each component part or as an assembled
unit.
1910.253(c)(1)(ii)
Except as provided in paragraph (c)(1)(iii) of this section fuel-gas cylinders connected to one
manifold inside a building shall be limited to a total capacity not exceeding 300 pounds (135.9 kg) of liquefied petroleum gas or 3,000 cubic feet (84
m(3)) of other fuel-gas. More than one such manifold with connected cylinders may be located in the same room provided the manifolds are at least 50
feet (15 m) apart or separated by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half
hour.
1910.253(c)(1)(iii)
Fuel-gas cylinders connected to one manifold having an aggregate capacity exceeding 300 pounds
(135.9 kg) of liquefied petroleum gas or 3,000 cubic feet (84 m(3)) of other fuel-gas shall be located outdoors, or in a separate building or room
constructed in accordance with paragraphs (f)(6)(i)(H) and (f)(6)(i)(I) of this section.
1910.253(c)(1)(iv)
Separate manifold buildings or rooms may also be used for the storage of drums of calcium
carbide and cylinders containing fuel gases as provided in paragraph (b)(3) of this section. Such buildings or rooms shall have no open flames for
heating or lighting and shall be well-ventilated.
..1910.253(c)(1)(v)
1910.253(c)(1)(v)
High-pressure fuel-gas manifolds shall be provided with approved pressure regulating
devices.
1910.253(c)(2)
High-pressure oxygen manifolds (for use with cylinders having a Department of Transportation service
pressure above 200 psig (1.36 MPa)).
1910.253(c)(2)(i)
Manifolds shall be approved either separately for each component part or as an assembled
unit.
1910.253(c)(2)(ii)
Oxygen manifolds shall not be located in an acetylene generator room. Oxygen manifolds shall be
separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible
barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.
1910.253(c)(2)(iii)
Except as provided in paragraph (c)(2)(iv) of this section, oxygen cylinders connected to one
manifold shall be limited to a total gas capacity of 6,000 cubic feet (168 m(3)). More than one such manifold with connected cylinders may be located
in the same room provided the manifolds are at least 50 feet (15 m) apart or separated by a noncombustible barrier at least 5 feet (1.5 m) high having
a fire-resistance rating of at least one-half hour.
..1910.253(c)(2)(iv)
1910.253(c)(2)(iv)
An oxygen manifold, to which cylinders having an aggregate capacity of more than 6,000 cubic
feet (168 m(3)) of oxygen are connected, should be located outdoors or in a separate noncombustible building. Such a manifold, if located inside a
building having other occupancy, shall be located in a separate room of noncombustible construction having a fire-resistance rating of at least
one-half hour or in an area with no combustible material within 20 feet (6.1 m) of the manifold.
1910.253(c)(2)(v)
An oxygen manifold or oxygen bulk supply system which has storage capacity of more than 13,000
cubic feet (364 m(3))of oxygen (measured at 14.7 psia (101 kPa) and 70 deg. F (21.1 deg. C)), connected in service or ready for service, or more than
25,000 cubic feet (700 m(3)) of oxygen (measured at 14.7 psia (101 kPa) and 70 deg. F (21.1 deg. C)), including unconnected reserves on hand at the
site, shall comply with the provisions of the Standard for Bulk Oxygen Systems at Consumer Sites, NFPA No. 566-1965.
1910.253(c)(2)(vi)
High-pressure oxygen manifolds shall be provided with approved pressure-regulating
devices.
1910.253(c)(3)
Low-pressure oxygen manifolds (for use with cylinders having a Department of Transportation service
pressure not exceeding 200 psig (1.36 MPa)).
1910.253(c)(3)(i)
Manifolds shall be of substantial construction suitable for use with oxygen at a pressure of 250
psig (1.7 MPa). They shall have a minimum bursting pressure of 1,000 psig (6.8 MPa) and shall be protected by a safety relief device which will
relieve at a maximum pressure of 500 psig (3.4 MPa). DOT-4L200 cylinders have safety devices which relieve at a maximum pressure of 250 psig (1.7 MPa)
(or 235 psig (1.6 MPa) if vacuum insulation is used).
..1910.253(c)(3)(ii)
1910.253(c)(3)(ii)
Hose and hose connections subject to cylinder pressure shall comply with paragraph (e)(5) of
this section. Hose shall have a minimum bursting pressure of 1,000 psig (6.8 MPa).
1910.253(c)(3)(iii)
The assembled manifold including leads shall be tested and proven gas-tight at a pressure of
300 psig (2.04 MPa). The fluid used for testing oxygen manifolds shall be oil-free and not combustible.
1910.253(c)(3)(iv)
The location of manifolds shall comply with paragraphs (c)(2)(ii), (c)(2)(iii), (c)(2)(iv), and
(c)(2)(v) of this section.
1910.253(c)(3)(v)
The following sign shall be conspicuously posted at each manifold:
Low-Pressure Manifold
Do Not Connect High-Pressure Cylinders
Maximum Pressure - 250 psig (1.7 MPa)
1910.253(c)(4)
Portable outlet headers.
1910.253(c)(4)(i)
Portable outlet headers shall not be used indoors except for temporary service where the
conditions preclude a direct supply from outlets located on the service piping system.
1910.253(c)(4)(ii)
Each outlet on the service piping from which oxygen or fuel-gas is withdrawn to supply a
portable outlet header shall be equipped with a readily accessible shutoff valve.
1910.253(c)(4)(iii)
Hose and hose connections used for connecting the portable outlet header to the service piping
shall comply with paragraph (e)(5) of this section.
..1910.253(c)(4)(iv)
1910.253(c)(4)(iv)
Master shutoff valves for both oxygen and fuel-gas shall be provided at the entry end of the
portable outlet header.
1910.253(c)(4)(v)
Portable outlet headers for fuel-gas service shall be provided with an approved hydraulic
back-pressure valve installed at the inlet and preceding the service outlets, unless an approved pressure-reducing regulator, an approved back-flow
check valve, or an approved hydraulic back-pressure valve is installed at each outlet. Outlets provided on headers for oxygen service may be fitted
for use with pressure-reducing regulators or for direct hose connection.
1910.253(c)(4)(vi)
Each service outlet on portable outlet headers shall be provided with a valve assembly that
includes a detachable outlet seal cap, chained or otherwise attached to the body of the valve.
1910.253(c)(4)(vii)
Materials and fabrication procedures for portable outlet headers shall comply with paragraphs
(d)(1), (d)(2), and (d)(5) of this section.
1910.253(c)(4)(viii)
Portable outlet headers shall be provided with frames which will support the equipment
securely in the correct operating position and protect them from damage during handling and operation.
..1910.253(c)(5)
1910.253(c)(5)
Manifold operating procedures.
1910.253(c)(5)(i)
Cylinder manifolds shall be installed under the supervision of someone familiar with the proper
practices with reference to their construction and use.
1910.253(c)(5)(ii)
All manifolds and parts used in methods of manifolding shall be used only for the gas or gases
for which they are approved.
1910.253(c)(5)(iii)
When acetylene cylinders are coupled, approved flash arresters shall be installed between each
cylinder and the coupler block. For outdoor use only, and when the number of cylinders coupled does not exceed three, one flash arrester installed
between the coupler block and regulator is acceptable.
1910.253(c)(5)(iv)
The aggregate capacity of fuel-gas cylinders connected to a portable manifold inside a building
shall not exceed 3,000 cubic feet (84 m(3)) of gas.
1910.253(c)(5)(v)
Acetylene and liquefied fuel-gas cylinders shall be manifolded in a vertical position.
1910.253(c)(5)(vi)
The pressure in the gas cylinders connected to and discharged simultaneously through a common
manifold shall be approximately equal.
1910.253(d)
Service piping systems -
1910.253(d)(1)
Materials and design.
|